[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1266792":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1266792,854,2,"多选题","下面关于水力警铃的叙述，正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","水力警铃应安装在公共通道或值班室附近的外墙上",true,{"key":16,"text":17,"correct":14},"B","水力警铃连接管道应采用镀锌钢管",{"key":19,"text":20,"correct":21},"C","水力警铃的启动压力不应小于0.1MPa",false,{"key":23,"text":24,"correct":14},"D","水力警铃的铃锤应转动灵活，无阻滞现象",{"key":26,"text":27,"correct":21},"E","水力警铃不需安装检修、测试的阀门","ABD","水力警铃应安装在公共通道或值班室附近的外墙上，且应安装检修、测试的阀门。连接管道应采用镀锌钢管，当镀锌钢管公称直径为20mm时，其长度不应大于20m；水力警铃的启动压力不应小于0.05MPa。水力警铃的铃锤应转动灵活，无阻滞现象。",{"id":6,"name":31,"category":32,"favorite":33},"(设备安装质量)专业管理实务 岗位知识","建筑工程",0]