[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1253105":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1253105,837,2,"多选题","防排烟系统正压送风的检测要求：（ ）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","防烟楼梯间为40~50Pa",true,{"key":16,"text":17,"correct":14},"B","前室、合用前室为25~30Pa",{"key":19,"text":20,"correct":21},"C","前室、合用前室为40~50Pa",false,{"key":23,"text":24,"correct":14},"D","消防电梯前室为25~30Pa",{"key":26,"text":27,"correct":14},"E","封闭避难层为25~30Pa","ABDE","3）防排烟系统联合试运转及调试①在风机室手动启动正压送风机，用微压仪测量正压送风系统余压值，楼梯间、室、走道风压呈递减趋势明显，并应符合下列要求:防烟楼梯间为40~50Pa;前室、用前室、消防电梯前室、封闭避难层（间）为25~30Pa。",{"id":6,"name":31,"category":32,"favorite":33},"(设备安装施工)基础知识","建筑工程",0]