[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1252395":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1252395,837,1,"单选题","非镀锌电缆桥架间连接板的两端跨接铜芯接地线，接地线最小允许截面积不小于（ ）m㎡。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1.5",false,{"key":16,"text":17,"correct":14},"B","2.5",{"key":19,"text":20,"correct":21},"C","4",true,{"key":23,"text":24,"correct":14},"D","6","金属电缆桥架及其支架和引人或引出的金属电缆导管必须接地（PE）或接零（PEN）可靠，且必须符合下列规定：a.金属电缆桥架及其支架全长应不少于2处与接地（PE）或接零（PEN）干线相连接；b.非镀锌电缆桥架间连接板的两端跨接铜芯接地线，接地线最小允许截面积不小于4m㎡；c.镀锌电缆桥架间连接板的两端不跨接接地线.，但连接板两端不少于2个有防松螺帽或防松垫圈的连接固定螺栓。",{"id":6,"name":27,"category":28,"favorite":29},"(设备安装施工)基础知识","建筑工程",0]