[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1153332":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1153332,804,2,"多选题","下列关于接地装置安装的说法，正确的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","接地引入线长度不宜超过30m",true,{"key":16,"text":17,"correct":18},"B","接地引入线可采用90mm2的铝导线",false,{"key":20,"text":21,"correct":18},"C","接地体埋深距地面应≥0.5m",{"key":23,"text":24,"correct":14},"D","接地体和接地体连接线必须焊接牢固，焊接点应进行防腐处理",{"key":26,"text":27,"correct":14},"E","设备机架应采用截面不小于16mm2多股铜线接地","ADE","接地引入线长度不应超过 30m。当采用热镀钵扁钢材料，截面积应不小于 40mm x4mm； 当采用铜芯电缆时，铜导线截面不小于 90mm2 。 接地体和接地体连接线连接处必须焊接牢固，对于所有接地装置的焊接点都要进行防腐处理。 接地体埋深上端距地面不应小于 700mm，在寒冷地区应在冻士层以下。",{"id":6,"name":31,"category":32,"favorite":33},"一建通信与广电工程实务","建筑工程",0]