[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1149985":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1149985,802,2,"多选题","关于热力管道直埋保温管接头的规定，以下正确的叙述是( )。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","接头施工采取的工艺应有合格的检验报告",true,{"key":16,"text":17,"correct":14},"B","接头外观不应出现过烧、鼓包、翘边、褶皱或层间脱离等现象",{"key":19,"text":20,"correct":21},"C","接头焊接完毕即可进行保温和密封",false,{"key":23,"text":24,"correct":14},"D","接头处的钢管表面应干净、干燥",{"key":26,"text":27,"correct":14},"E","接头外护层安装完成后，必须全部进行气密性检验并应合格","ABDE","2020\u002F2019教材P469 直埋保温管接头的保温和密封应符合下列规定：（1)接头施工采取的工艺应有合格的形式检验报告。（2)保温前接头处钢管表面应干净、干燥，接头保温必须采用机械式发泡。（3)保温接头发泡后，发泡孔应及时进行密封。（4)接头发泡的工艺操作温度应在15-4 5℃的范围内。（5)接头外观不应出现过烧、鼓包、翘边、褶皱或层间脱离等现象。",{"id":6,"name":31,"category":32,"favorite":33},"一建市政公用工程实务","建筑工程",0]