[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1148766":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1148766,802,1,"单选题","供热站所所有系统应进行严密性试验，试验压力为1.25倍设计压力，且不得低于（ ），稳压在1h内，详细检查管道、焊缝、管路附件及设备等无渗漏，压力降不大于0.05MPa为合格。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.5MPa",false,{"key":16,"text":17,"correct":18},"B","0.6MPa",true,{"key":20,"text":21,"correct":14},"C","0.4MPa",{"key":23,"text":24,"correct":14},"D","0.8MPa","2020教材P229 \u002F 2019教材P230 试验压力为1.25倍设计压力，且不得低于0.6MPa，稳压在l h内，详细检查管道、焊缝、管路附件及设备等无渗漏，压力降不大于0.05MPa为合格。",{"id":6,"name":27,"category":28,"favorite":29},"一建市政公用工程实务","建筑工程",0]