[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1148765":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1148765,802,1,"单选题","某供热管网设计压力为0.4MPa，其严密性试验压力（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","0.42",false,{"key":16,"text":17,"correct":14},"B","0.46",{"key":19,"text":20,"correct":14},"C","0.50",{"key":22,"text":23,"correct":24},"D","0.60",true,"2020教材P229 \u002F 2019教材P230 三、严密性试验：（4）严密性试验压力为设计压力的1.25倍，且不小于0.6MPa。一级管网和供热站内管道及设备，在试验压力下稳压1h，前后压降不大于0.05MPa,检査管道、焊缝、管路附件及设备无渗漏，固定支架无明显变形，则为合格；二级管网在试验压力下稳压30min，前后压降不大于0.05MPa,且管道、焊缝、管路附件及设备无渗漏，固定支架无明显变形的为合格。",{"id":6,"name":27,"category":28,"favorite":29},"一建市政公用工程实务","建筑工程",0]