[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1145320":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1145320,800,2,"多选题","关于高分子合成材料进行阻燃处理的说法，正确的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","顶棚采用的泡沫塑料应涂刷耐火极限大于30min的超薄型钢结构防火涂料",true,{"key":16,"text":17,"correct":14},"B","顶棚采用的泡沫塑料应涂刷一级饰面型防火涂料，湿涂覆比值应大于500g\u002Fm2",{"key":19,"text":20,"correct":14},"C","B1级塑料电工套管不宜明敷",{"key":22,"text":23,"correct":24},"D","B1级塑料电工管套明敷时，应明敷在B1级材料表面",false,{"key":26,"text":27,"correct":24},"E","塑料电工套管穿过B2级（含B2级）的装修材料时，应采用B1级材料或防火封堵密封件严密封堵","ABC","2020教材P370 \u002F 2019教材P371 （1）顶棚采用塑料泡沫时，应涂刷防火涂料。防火涂料宜选用耐火极限大于30min的超薄型钢结构防火涂料或一级饰面型防火涂料，湿涂覆比值应大于500g\u002Fm2.涂刷均匀，且涂刷不应少于2次。 （2）塑料电工套管的施工应满足以下要求： 1）B2级塑料电工套管不得明敷； 2）B1级塑料电工套管明敷时，应明敷在A级材料表面； 3）塑料电工套管穿过B1级以下（含B1级）的装修材料时，应采用A级材料或防火封堵密封件严密封堵。",{"id":6,"name":31,"category":32,"favorite":33},"一建建筑工程实务","建筑工程",0]