[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1137324":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1137324,797,2,"多选题","（2020年真题）关于建筑电气工程母线槽安装的说法，正确的有()。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","绝缘测试应在母线槽安装前后分别进行",true,{"key":16,"text":17,"correct":14},"B","照明母线槽的垂直偏差不应大于10mm",{"key":19,"text":20,"correct":21},"C","母线槽接口穿越楼板处应设置补偿装置",false,{"key":23,"text":24,"correct":14},"D","母线槽连接部件应与本体防护等级一致",{"key":26,"text":27,"correct":14},"E","母线槽连接处的接触电阻应小于0.1Ω","ABDE","P178-189 母线槽直线段安装应平直，配电母线槽水平度和垂直度偏差不宜大于千分之1.5；全长最大偏差不宜大于20mm,照明母线槽水平偏差全长不应大于5mm，垂直骗你查不应大于10mm. 母线槽跨越建筑变形缝处时，应设置补偿装置，母线槽直线敷设长度超过80m，每50-60m宜设置伸缩节。 母线槽连接部件的防护等级应与母线槽本体的防护等级一致。 母线槽连接的接触电阻不小于0.1欧姆。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]