[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1137323":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1137323,797,2,"多选题","（2018年真题）下列灯具中，需要与保护导体连接的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","离地 5m 的Ⅰ类灯具",true,{"key":16,"text":17,"correct":18},"B","采用 36V 供电的灯具",false,{"key":20,"text":21,"correct":18},"C","地下一层的Ⅱ类灯具",{"key":23,"text":24,"correct":14},"D","等电位连接的灯具",{"key":26,"text":27,"correct":18},"E","采取电气隔离的灯具","AD","（1）Ⅰ类灯具的防触电保护不仅依靠基本绝缘，还需把外露可导电部分连接到保护导体上，因 此Ⅰ类灯具外露可导电部分必须采用铜芯软导线与保护导体可靠连接，连接处应设置接地标识；铜芯软导 线（接地线）的截面应与进入灯具的电源线截面相同，导线间的连接应采用导线连接器或缠绕搪锡连接。 （2）Ⅱ类灯具的防触电保护不仅依靠基本绝缘，还具有双重绝缘或加强绝缘，因此Ⅱ类灯具外壳不需要 与保护导体连接。 （3）Ⅲ类灯具的防触电保护是依靠安全特低电压，电源电压不超过交流 50V，采用隔离变压器供电。因此 Ⅲ类灯具的外壳不容许与保护导体连接",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]