[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1137319":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1137319,797,2,"多选题","（2020年真题）关于建筑室内给水管道支吊架安装的说法，正确的有()。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","滑动支架的滑托与滑槽应有3~5mm间隙",true,{"key":16,"text":17,"correct":14},"B","无热伸长管道的金属管道吊架应垂直安装",{"key":19,"text":20,"correct":21},"C","有热伸长管道的吊架应向热膨胀方向偏移",false,{"key":23,"text":24,"correct":14},"D","6m高楼层的金属立管管卡每层不少于2个",{"key":26,"text":27,"correct":14},"E","塑料管道与金属支架之间应加衬非金属垫","ABDE","P168-177 管道支吊架安装 （1）滑动支架应灵活，滑托于滑槽两侧应留有3--5mm间隙，纵向移动量应符合设计要求 （2）无热伸长管道的吊架，吊杆应垂直安装 （3）有热伸长管道的吊架，吊杆应向热膨胀的反方向偏移 （4）塑料管及复合管垂直或水平安装的支架之间应符合规范的规定，采用金属制作的管道支架，应在管道与支架间加衬非金属垫或套管 （5）金属管道立管管卡安装应符合下列规定：楼层高度小于或等于5cm，每层必须安装1个；楼层高度大于5米，每层不得少于2个；管卡安装高度，距地面应为1.5-1.8m，2个以上管卡应匀称安装，统一房间管卡应安装在同一高度上。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]