[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1137234":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1137234,797,2,"多选题","下列在有爆炸性气体环境中电气设备接地要求做法错误的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","接地干线应在爆炸危险区域内不同的方向不少于两处与接地体连接",false,{"key":16,"text":17,"correct":18},"B","电气设备的接地装置与独立的避雷针的接地装置应合并设置；与建筑物上的避雷针接地装置可分开设置",true,{"key":20,"text":21,"correct":14},"C","在有爆炸危险的环境中，电气设备的金属外壳应可靠接地",{"key":23,"text":24,"correct":14},"D","在有爆炸性气体环境1区内的所有电气设备应采用专门的接地线",{"key":26,"text":27,"correct":18},"E","在有爆炸性气体环境2区内所有电气设备，应采用专门的接地线","BE","电气设备的接地装置与独立的避雷针的接地装置应分开设置；与建筑物上的避雷针接地装置可合并 设置。在有爆炸性气体环境1区内的所有电气设备以及2区内除照明灯具外的其他电气设备，应采用专门的接地线。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]