[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1137089":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1137089,797,2,"多选题","在架空电力线路保护区取土时，应遵守的规定内容有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","取土范围",true,{"key":16,"text":17,"correct":18},"B","取土时间",false,{"key":20,"text":21,"correct":14},"C","取土坡度",{"key":23,"text":24,"correct":14},"D","预留通道",{"key":26,"text":27,"correct":18},"E","取土土质","ACD","2020版教材P456 \u002F 2019版教材P444 3.保护区内取土规定：（1）取土范围的规定。各电压等级的杆塔周围禁止取土的范围是：35kV、110~220kV、330~500kV的范围分别为4m、5m、8m。（2）取土坡度规定。一般不得大于45°。特殊情况由县以上地方电力主管部门另定。（3）预留通道规定。取土时必须预留巡视、检修线路的人员、车辆通行的通道。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]