[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136933":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136933,797,2,"多选题","关于DCS机柜的接地要求，正确的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","DCS机柜需单独接地",true,{"key":16,"text":17,"correct":18},"B","接地点到防雷接地距离需大于5m",false,{"key":20,"text":21,"correct":14},"C","机柜与底座间铺设绝缘材料",{"key":23,"text":24,"correct":18},"D","总接地电阻小于4Ω",{"key":26,"text":27,"correct":18},"E","机柜与底座连接螺栓选用镀锌店垫片","AC","2020版教材P142 \u002F 2019版教材P132 DCS系统，1）单独接地，不与其他系统共用接地点或接地线。2）接地点到防雷接地或高压电气设备接地点的距离需大于10m。3）每个机柜的系统电源地、信号屏蔽地、机柜安全地分别汇总接至电源柜三根铜排上，分别引至总接地点，走线尽量短而直，总接地电阻小于3Ω。4）DCS机柜要求浮空，底座与机柜间铺设绝缘材料，盘柜与底座连接螺栓应带绝缘垫片。5）DCS远程控制站和智能采集前端就近接人电气全厂接地网。（2）其他盘柜如无特殊要求，一般底座应就近接入电气全厂接地网。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]