[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136878":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136878,797,2,"多选题","10kV电缆线路敷设后，正确的电缆绝缘电阻测量方法有（）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","使用2500V兆欧表测量",true,{"key":16,"text":17,"correct":14},"B","测量前将电缆接地放电",{"key":19,"text":20,"correct":14},"C","当接地线路较长时，放电时间不得少于1min",{"key":22,"text":23,"correct":24},"D","测量时间应不少于10min",false,{"key":26,"text":27,"correct":14},"E","测量后电缆应再次接地放电","ABCE","2020版教材P88 \u002F 2019版教材P77 （三）绝缘电阻测量：（1）1KV以上电缆可用2500V兆欧表测量其绝缘电阻。（2）测量前用导线将电缆对地短路放电，当接地线路较长或绝缘性能良好，放电时间不得少于1分钟。（3）测量完毕或需要再次测量时，应当再次接地放电。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]