[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136877":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136877,797,2,"多选题","金属储罐等防静电的接地要求有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","防静电的接地装置应单独设置",false,{"key":16,"text":17,"correct":18},"B","接地线应单独与接地干线相连",true,{"key":20,"text":21,"correct":18},"C","接地线的连接螺栓不应小于M10",{"key":23,"text":24,"correct":18},"D","防静电的接地装置可共同设置",{"key":26,"text":27,"correct":14},"E","并列防静电接地可以串联连接","BCD","2020版教材P90 \u002F 2019版教材P80 五、防静电接地装置的要求。1.防静电的接地装置可与防感应雷和电气设备的接地装置共同设置。只做防静电的接地装置，每一处接地体的接地电阻应符合设计规定。2.设备、机组、储罐、管道等的防静电接地线，应单独与接地体或接地干线相连，除并列管道外不得互相串联接地。3.防静电接地线的安装，应与设备、机组、储罐等固定接地端子或螺栓连接，连接螺栓不应小于M10,并有防松装置和涂以电力复合脂。 4. 容量为50m3及以上的储罐，其接地点不应少于两处，且接地点的间距不应大于30m ，并应在罐体底音1)周围对称与接地体相连，接地体应连接成环形的闭合回路.",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]