[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136801":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136801,797,2,"多选题","空调设备的监控系统中，温度传感器至现场控制器之间的连接要求有（）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","镍温度传感器的接线电阻应小于3Ω",true,{"key":16,"text":17,"correct":14},"B","铂温度传感器的接线电阻应小于1Ω",{"key":19,"text":20,"correct":14},"C","屏蔽线缆的接地应在现场控制器侧",{"key":22,"text":23,"correct":24},"D","温度传感器的连接线采用同轴电缆",false,{"key":26,"text":27,"correct":24},"E","屏蔽线缆的接地点应在金属管路侧","ABC","2020版教材P212 \u002F 2019版教材P199 （4）传感器至现场控制器之间的连接应符合设计要求。例如，镍温度传感器的接线电阻应小于3Ω，铂温度传感器的接线电阻应小于1Ω，并在现场控制器侧接地。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]