[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136784":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136784,797,2,"多选题","关于冷却塔的要求，正确的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","冷却塔与基座的连接必须用不锈钢螺栓",false,{"key":16,"text":17,"correct":18},"B","冷却塔的水平度和垂直度允许偏差为2‰",true,{"key":20,"text":21,"correct":18},"C","多台开式冷却塔的水面高度应一致，高度偏差值不应大于30mm",{"key":23,"text":24,"correct":18},"D","冷却塔进风侧距建筑物应大于1m",{"key":26,"text":27,"correct":18},"E","标高应符合设计要求，允许误差应为±20mm","BCDE","2020版教材P199 \u002F 2019版教材P187 2.冷却塔安装要求（1）基础的位置、标高应符合设计要求，允许误差应为±20mm。进风侧距建筑物应大于1m。冷却塔部件与基座的连接应采用镀锌或不锈钢螺栓，固定应牢固。（2）冷却塔安装应水平，单台冷却塔的水平度和垂直度允许偏差应为2‰。多台冷却塔安装时，排列应整齐，各台开式冷却塔的水面高度应一致，高度偏差值不应大于30mm。当采用共用集管并联运行时，冷却塔集水盘（槽）之间的连通管应符合设计要求。（3）冷却塔的集水盘应严密、无渗漏，进、出水口的方向和位置应正确。静止分水器的布水应均匀；转动布水器喷水出口方向应一致，转动应灵活，水量应符合设计或产品技术文件的要求。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]