[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136780":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136780,797,2,"多选题","建筑电气工程中，接闪带的安装要求有（）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","接闪带的固定支架高度不宜小于150mm",true,{"key":16,"text":17,"correct":14},"B","每个固定支架应能承受49N的垂直拉力",{"key":19,"text":20,"correct":21},"C","镀锌扁钢接闪带的连接应采用螺栓搭接",false,{"key":23,"text":24,"correct":14},"D","接闪带在变形缝处的跨接应有补偿措施",{"key":26,"text":27,"correct":21},"E","接闪带与防雷引下线必须采用焊接连接","ABD","2020版教材P188 \u002F 2019版教材P177 （2）接闪线和接闪带安装要求： 1）接闪线和接闪带安装应平正顺直、无急弯。 2）固定支架高度不宜小于150mm,固定支架应间距均匀，支架间距应符合规范的规定。 3）每个固定支架应能承受49N的垂直拉力。 （3）防雷引下线、接闪线、接闪网、接闪带的焊接连接应符合规范的搭接要求。 （4）接闪带或接闪网在过建筑物变形缝处的跨接应有补偿措施。 （5）当利用建筑物金属屋面或屋顶上旗杆、栏杆、装饰物、铁塔、女儿墙上的盖板等永久性金属物作接闪器时，其材质及截面应符合设计要求，建筑物金属屋面板间的连接、永久性金属物各部件之间的连接应可靠、持久。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]