[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136773":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136773,797,2,"多选题","建筑电气工程中，母线槽的安装连接要求有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","配电母线槽水平度偏差不宜大于1.5‰",true,{"key":16,"text":17,"correct":18},"B","照明母线槽水平偏差全长不应大于10㎜",false,{"key":20,"text":21,"correct":14},"C","照明母线槽垂直偏差全长不应大于10㎜",{"key":23,"text":24,"correct":14},"D","母线应与外壳同心，允许偏差应为±5㎜",{"key":26,"text":27,"correct":18},"E","母线槽直线敷设长度超过50m设置伸缩节","ACD","2020版教材P179 \u002F 2019版教材P168 3.母线槽安装连接要求（1）母线槽直线段安装应平直，配电母线槽水平度与垂直度偏差不宜大于1.5‰，全长最大偏差不宜大于20mm;照明母线槽水平偏差全长不应大于5mm。垂直偏差不应大于10mm。母线应与外壳同心，允许偏差应为±5mm。（2）母线槽跨越建筑物变形缝处时，应设置补偿装置；母线槽直线敷设长度超过80m，每50~60m宜设置伸缩节。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]