[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136769":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1136769,797,2,"多选题","建筑电气工程中，柔性导管敷设的要求有（）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","柔性导管的长度在动力工程中不宜大于0.8m",true,{"key":16,"text":17,"correct":14},"B","柔性导管的长度在照明工程中不宜大于1.2m",{"key":19,"text":20,"correct":14},"C","柔性导管与刚性导管的连接应采用专用接头",{"key":22,"text":23,"correct":14},"D","金属柔性导管不应作为保护导体的连续导体",{"key":25,"text":26,"correct":27},"E","埋设在混凝土内的导管可采用金属柔性导管",false,"ABCD","2020版教材P182 \u002F 2019版教材P171 6.可弯曲金属导管及柔性导管敷设要求（1）刚性导管经柔性导管与电气设备、器具连接时，柔性导管的长度在动力工程中不宜大于0.8m，在照明工程中不宜大于1.2m。（2）可弯曲金属导管或柔性导管与刚性导管或电气设备、器具间的连接应采用专用接头。（3）当可弯曲金属导管有可能受重物压力或明显机械撞击时，应采取保护措施。（4）明配金属、非金属柔性导管固定点间距应均匀，不应大于1m,管卡与设备、器具、弯头中点、管端等边缘的距离应小于（5）可弯曲金属导管和金属柔性导管不应作为保护导体的接续导体。",{"id":6,"name":31,"category":32,"favorite":33},"一建机电工程实务","建筑工程",0]