[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1136182":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1136182,797,1,"单选题","输送极度危害、高度危害流体以及可燃流体的管道在耐压试验合格后应进行（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","气压试验",false,{"key":16,"text":17,"correct":14},"B","气密性试验",{"key":19,"text":20,"correct":14},"C","液压试验",{"key":22,"text":23,"correct":24},"D","泄漏试验",true,"2020版教材P102 \u002F 2019版教材P92 管道泄漏性试验的实施要点 ( 1 )输送极度和高度危害介质以及可燃介质的管道，必须进行泄漏性试验。 ( 2 )泄漏性试验应在压力试验合格后进行，试验介质宜采用空气。 ( 3 )泄漏性试验压力为设计压力。 ( 4 )泄漏性试验可结合试车一并进行。 ( 5 )泄漏试验应逐级缓慢升压，当达到试验压力，并且停压10min后，采用涂刷中性发泡剂等方法巡回检查阀门填料函、法兰或者螺纹连接处、放空阀、排气阀、排水阀等所有密封点无泄漏为合格。",{"id":6,"name":27,"category":28,"favorite":29},"一建机电工程实务","建筑工程",0]