[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1135709":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1135709,797,1,"单选题","接闪器安装不符合要求的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","应进行检查。接闪器组装时，各节位置符合出厂标志的编号",false,{"key":16,"text":17,"correct":14},"B","排气式接闪器的安装，应避免其排出的气体引起相间或对地闪络，不能喷及其他电气设备",{"key":19,"text":20,"correct":14},"C","氧化锌接闪器的接地线应用截面积不小于16mm2的软铜线",{"key":22,"text":23,"correct":24},"D","管型接闪器与被保护设备的连接线长度不得大于5m",true,"2020版教材P89 \u002F 2019版教材P79 接闪器安装前，应进行检查。接闪器组装时，各节位置符合出厂标志的编号。 排气式接闪器的安装，应避免其排出的气体引起相间或对地闪络，不能喷及其他电气设备。 氧化锌接闪器的接地线应用截面积不小于16mm2的软铜线；安装时要注意接闪器上端带电部分与电器柜体外壳或柜内其他设备的安全距离； 管型接闪器与被保护设备的连接线长度不得大于4m；",{"id":6,"name":27,"category":28,"favorite":29},"一建机电工程实务","建筑工程",0]