[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1127236":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1127236,792,2,"多选题","供热管道保温层施工符合相关规定的是（）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","保温棉毡、垫的密度应均匀",true,{"key":16,"text":17,"correct":14},"B","管道端部或有盲板的部位应敷设保温层",{"key":19,"text":20,"correct":21},"C","当采用半硬质保温制品施工时，应预设伸缩缝",false,{"key":23,"text":24,"correct":21},"D","瓦块式保温制品的拼缝宽度不得大于3mm",{"key":26,"text":27,"correct":14},"E","阀门、法兰等部位的保温结构应易于拆装","ABE","P145-151 保温层施工应符合下列规定: 1)保温棉毡、垫的密实度应均匀，外形应规整，保温厚度和重度应符合设计要求。 2)管道端部或有盲板的部位应做保温。 3)当采用硬质保温制品施工时，应按设计要求预留伸缩缝。 4)瓦块式保温制品的拼缝宽度不得大于5mm。 5)保温结构不应影响阀门、法兰的更换及维修。靠近法兰处，应在法兰的一侧留出螺栓长度加25mm的空隙。有冷紧或热紧要求的法兰，应在完成后再进行保温。",{"id":6,"name":31,"category":32,"favorite":33},"二建市政工程实务","建筑工程",0]