[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1126256":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1126256,792,1,"单选题","（2015年真题）关于城镇供热直埋保温接头的说法，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","一级管网现场安装的85%的接头进行气密性检验",true,{"key":16,"text":17,"correct":18},"B","接头的保温和密封应在结构焊口检验合格后方可进行",false,{"key":20,"text":21,"correct":18},"C","预警线断路、短路检测应在接头安装完毕后进行",{"key":23,"text":24,"correct":18},"D","外观检查是质量验收的主控项目","本题考核的是城镇供热直埋保温管接头的保温和密封的规定。一级管网的现场安装的接头密封应进行100%的气密性检验，二级管网的现场安装的接头密封应进行不少于20%的气密性检验。气密性检验的压力为0.02MPa，用肥皂水仔细检查密封处，无气泡为合格。这次二建考试对质量与验收考核的内容比较多。此题的干扰项在C，在教材中，“报警线在安装前应测试报警线的通断情况和电阻值”这句话。",{"id":6,"name":27,"category":28,"favorite":29},"二建市政工程实务","建筑工程",0]