[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1114029":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1114029,787,2,"多选题","关于变风量空调系统非设计满负荷条件下联合调试的要求，正确的有（ ）。2019",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","系统总风量实测值与设计风量的偏差不应大于10%",false,{"key":16,"text":17,"correct":18},"B","系统空气处理机组应能在设计参数范围内对风机实现变频调速",true,{"key":20,"text":21,"correct":18},"C","空气处理机组新风量实测值与设计新风量的允许偏差为0~+10%",{"key":23,"text":24,"correct":18},"D","空调冷（热）水系统、冷却水系统总流量与设计流量的偏差不应大于10%",{"key":26,"text":27,"correct":14},"E","各变风量末端装置的最大风量调试结果与设计风量的偏差不应大于-5%~+15%","BCD","系统非设计满负荷条件下的联合试运转及调试应符合下列规定： （1）系统总风量调试结果与设计风量的偏差不应大于-5%～+10%；建筑内各区域的压差应符合设计要求。 （2）变风量空调系统联合调试应符合下列规定： 1）系统空气处理机组应能在设计参数范围内对风机实现变频调速。 2）空气处理机组在设计机外余压条件下，系统总风量应满足风量偏差不应大于-5%～+10%的要求；新风量与设计新风量的允许偏差为0～+10%。 3）各变风量末端装置的最大风量调试结果与设计风量的偏差不应大于0～+15%。 （3）空调冷（热）水系统、冷却水系统总流量与设计流量的偏差不应大于10%。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]