[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1114009":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1114009,787,2,"多选题","关于照明配电箱的安装技术要求，正确的有（）。2016",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","插座为单独回路时的插座数量不宜超过10个",true,{"key":16,"text":17,"correct":14},"B","零线和保护接地线应在汇流排上连接",{"key":19,"text":20,"correct":21},"C","配电箱内应标明用电回路的名称和功率",false,{"key":23,"text":24,"correct":14},"D","每个单相分支回路的灯具数量不宜超过25个",{"key":26,"text":27,"correct":21},"E","每个三相分支回路的电流不宜超过16A","ABD","本题考查的是电气照明施工技术要求。1）照明配电箱内应分别设置零线和保护接地（PE线）汇流排，零线和保护线应在汇流排上连接，不得绞接。2）照明配电箱内每一单相分支回路的电流不宜超过16A，灯具数量不宜超过25个。大型建筑组合灯具每一单相回路电流不宜超过25A，光源数量不宜超过60个。3）插座为单独回路时，数量不宜超过10个。灯具和插座混为一个回路时，其中插座数不宜超过5个。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]