[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113969":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113969,787,2,"多选题","（2020年真题）关于电力架空线路架设及试验的说法中，正确的有（ ）",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","导线连接电阻不应超过同长度导线电阻的2倍",false,{"key":16,"text":17,"correct":18},"B","检查架空线各相两侧的相位应一致",true,{"key":20,"text":21,"correct":18},"C","在额定电压下对空载线路的冲击合闸试验应进行3次",{"key":23,"text":24,"correct":14},"D","导线连接处的机械强度不应低于导线强度的测温仪90%",{"key":26,"text":27,"correct":18},"E","检验导线接头的连接质量可用红外线测温仪","BCE","P61-74 导线连接要求： （1）导线连接应接触良好，其接触电阻不应超过同长度导线电阻的1.2倍; （2）导线连接处应有足够的机械强度，其强度不应低于导线强度的95%; 电力架空线路试验： 1．测量线路的绝缘电阻应不小于验收规范规定; 2．检查架空线各相的两侧相位应一致; 3．在额定电压下对空载线路的冲击合闸试验应进行3次; 4．杆塔防雷接地线与接地装置焊接，测量杆塔的接地电阻值应符合设计的规定; 5．用红外线测温仪，测量导线接头的温度，来检验接头的连接质量。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]