[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113967":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113967,787,2,"多选题","正确的电缆直埋敷设做法有（）。2016",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","电缆敷设后铺100mm 厚的细沙再盖混凝土保护板",true,{"key":16,"text":17,"correct":14},"B","铠装电缆的金属保护层可靠接地",{"key":19,"text":20,"correct":21},"C","沟底铺设100mm 厚碎石",false,{"key":23,"text":24,"correct":14},"D","电缆进入建筑物时采用金属管保护",{"key":26,"text":27,"correct":21},"E","电缆可平行敷设在管道的上方","ABD","本题考查的是电力电缆的施工技术要求。D选项有争议，教材没有具体说明穿管的材质，实际施工过程中一般用金属管保护。 1）直埋电缆应使用铠装电缆，在铠装电缆的金属外皮要可靠接地，接地电阻不得大于10Ω 2）开挖的沟底是松软土层时，可直接敷设电缆，一般电缆埋深应不小于0.7m，穿越农田时应不小于1m。如果有石块或硬质杂物要铺设100mm厚的软土或细沙。 3）电缆敷设后，上面要铺100mm厚的软土或细沙，再盖上混凝土保护板，覆盖宽度应超过电缆两侧以外各50mm。 4）直埋电缆在直线段每隔50～100m处、电缆接头处、转弯处、进入建筑物等处应设置明显的方位标志或标桩。 5）电缆互相交叉.与非热力管和管道交叉穿越公路和墙壁时都要穿在保护管中，保护管长度超出交叉点1m，交叉净距不应小于250mm，保护管内径不应小于电缆外径的1.5倍。严禁将电缆平行敷设于管道的上方或下方。@##",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]