[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113892":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113892,787,2,"多选题","施工现场临时用电安全技术要求包括（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","配电箱的电器安装板上必须分设N线端子板和PE线端子板",true,{"key":16,"text":17,"correct":18},"B","N线端子板必须与金属电器安装板可靠连接",false,{"key":20,"text":21,"correct":14},"C","两级漏电保护器的额定动作电流和额定动作时间应作合理配合",{"key":23,"text":24,"correct":18},"D","首级开关箱的漏电开关的额定动作电流不应大于30mA",{"key":26,"text":27,"correct":14},"E","末级开关箱的漏电开关的额定动作时间不应大于0.1s","ACE","2020版教材P342 本题考查的是建设用电的规定。配电箱的电器安装板上必须分设N线端子板和PE线端子板。N线端子板必须与金属电器安装板绝缘，PE线端子板必须与金属电器安装板做电气连接。 两级漏电保护器的额定动作电流和额定动作时间应作合理配合，使之具有分级分段保护功能。末级开关箱的漏电开关的额定动作电流不应大于30mA，额定动作时间不应大于0.1s。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]