[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113767":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113767,787,2,"多选题","火灾自动报警系统设备安装要求包括（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","端子箱和模块箱宜设置在弱电间内",true,{"key":16,"text":17,"correct":18},"B","控制室引出的干线和火灾报警器及其他的控制线路应一起绑扎成束",false,{"key":20,"text":21,"correct":14},"C","端子板左侧为干线",{"key":23,"text":24,"correct":18},"D","设备接地采用镀锌扁铁",{"key":26,"text":27,"correct":14},"E","工作接地线与保护接地线应分开","ACE","2020版教材P158 本题考查的是建筑智能化系统设备安装技术规定。火灾自动报警系统设备安装：（1）端子箱和模块箱宜设置在弱电间内，应根据设计高度固定在墙壁上，安装时应端正牢固。（2）消防控制室引出的干线和火灾报警器及其他的控制线路应分别绑扎成束，汇集在端子板两侧，左侧应为干线，右侧应为控制线路。（3）设备接地应采用铜芯绝缘导线或电缆，不得利用镀锌扁铁或金属软管；消防控制设备的外壳及基础应可靠接地，接地线应引入接地端子箱；消防控制室应根据设计要求设置专用接地箱作为工作接地，工作接地线与保护接地线应分开。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]