[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113747":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113747,787,2,"多选题","关于风管系统安装要点包括（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","切断支吊架的型钢应采用机械加工",true,{"key":16,"text":17,"correct":14},"B","支吊架不宜设在风口、阀门、检查门、自控装置处",{"key":19,"text":20,"correct":21},"C","输送含有腐蚀介质的气体的风管应采用硬聚氯乙烯",false,{"key":23,"text":24,"correct":21},"D","风管穿过需要封闭的防火墙体或楼板时，应设厚度不小于1.5mm的预埋管或防护套管",{"key":26,"text":27,"correct":14},"E","风管与防护套管之间应采用不燃柔性材料封堵","ABE","2020版教材P147 本题考查的是通风空调风管系统的技术要求。切断支、吊、托架的型钢及其开螺孔应采用机械加工，不得用电气焊切割；支、吊架不宜设置在风口、阀门、检查门及自控装置处。防、排烟系统或输送温度高于70℃的空气或烟气，应采用耐热橡胶板或不燃的耐温、防火材料；输送含有腐蚀介质的气体，应采用耐酸橡胶板或软聚氯乙烯板。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]