[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113745":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113745,787,2,"多选题","下列金属风管中，应采取加固措施的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","直径800mm，长度1200mm的圆形风管",false,{"key":16,"text":17,"correct":18},"B","直径1000mm，长度1500mm的螺旋风管",true,{"key":20,"text":21,"correct":18},"C","总表面积5m2的圆形风管",{"key":23,"text":24,"correct":14},"D","边长650mm，长度1000mm低压矩形风管",{"key":26,"text":27,"correct":18},"E","单边面积大于1.5m2中压风管","BCE","2020版教材P147 本题考查的是通风空调风管系统的技术要求。对于满足下列条件的金属风管应采取加固措施： （1）圆形风管直径大于等于800mm，螺旋风管直径大于等于1000mm，且其管段长度大于1250mm或总表面积大于4m2。 （2）低压矩形风管边长大于630mm或矩形保温风管边长大于800mm，管段长度大于1250mm或单边面积大于1.2m2，中、高压风管单边面积大于1.0m2。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]