[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113739":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113739,787,2,"多选题","洁净空调系统的风管连接处必须严密，法兰垫料应采用（ ）的弹性材料。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","耐油橡胶",false,{"key":16,"text":17,"correct":14},"B","耐酸橡胶",{"key":19,"text":20,"correct":14},"C","硬质光滑",{"key":22,"text":23,"correct":24},"D","不产尘",true,{"key":26,"text":27,"correct":24},"E","不易老化","DE","2020版教材P151 2、风管系统安装的技术要点洁净空调系统的风管安装同样对其清洁程度和严密性有更高的要求。例如，风管安装前对施工现场彻底清扫，做到无尘作业，并应建立有效的防尘措施。经清洗干净包装密封的风管及部件，安装前不得拆除。如安装中间停顿，应将端口重新封好。风管连接处必须严密，法兰垫料应采用不产尘和不易老化的弹性材料，严禁在垫料表面刷涂料，法兰密封垫应尽量减少接头，接头采用阶梯或企口形式。风管与洁净室吊顶、隔墙等围护结构的穿越处应严密，可设密封填料或密封胶，不得有渗漏现象发生。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]