[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113730":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113730,787,2,"多选题","有关导线敷设要求的说法，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","线路绝缘电阻应大于0.5MΩ",true,{"key":16,"text":17,"correct":18},"B","同一台设备的3个电动机的回路可共用一个导管",false,{"key":20,"text":21,"correct":14},"C","交流与直流的导线不得穿在同一管内",{"key":23,"text":24,"correct":14},"D","同一交流回路的导线应穿同一根钢管内",{"key":26,"text":27,"correct":18},"E","导线在管内的接头应连接牢固","ACD","2020版教材P138 导线敷设要求： 3）管内导线应采用绝缘导线。 8）导线敷设后，应用500V兆欧表测试绝缘电阻，线路绝缘电阻不应小于0.5MΩ。 3）不同回路、不同电压等级、交流与直流的导线不得穿在同一管内。 4）绝缘导线的接头应设置在专用接线盒（箱）或器具内，不得敷设在导管内 5）槽盒内的绝缘导线总截面积不应超过槽盒截面积的40%。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]