[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113723":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113723,787,2,"多选题","关于导线的敷设要求，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","管内导线应采用绝缘导线",true,{"key":16,"text":17,"correct":14},"B","线路绝缘电阻不应小于0.5MΩ",{"key":19,"text":20,"correct":21},"C","管内导线总数不应多于10根",false,{"key":23,"text":24,"correct":14},"D","导线在管内不应有接头",{"key":26,"text":27,"correct":21},"E","管内导线不应大于管子截面积的60%","ABD","2020版教材P138 导线敷设要求： 1）管内导线应采用绝缘导线，A、B、C相线绝缘层颜色分别为黄绿红，保护接地线绝缘层为黄绿双色，零线绝缘层为淡蓝色。 2）导线敷设后，应用500V兆欧表测试绝缘电阻，线路绝缘电阻不应小于0.5MΩ。 3）不同回路、不同电压等级、交流与直流的导线不得穿在同一管内。但电压为50V及以下的回路；同一台设备的电动机回路和无干扰要求的控制回路；照明花灯的所有回路；同类照明的几个回路可穿入同一根管内，但管内导线总数不应多于8根。 4）同一交流回路的导线应穿同一根钢管内。导线在管内不应有接头，接头应设在接线盒（箱）内。 5）管内导线包括绝缘层在内的总截面积，不应大于管子内空截面积的40%。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]