[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113718":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113718,787,2,"多选题","母线槽的施工技术要求包括（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","每节母线槽的绝缘电阻值不应小于0.5MΩ",false,{"key":16,"text":17,"correct":14},"B","母线槽必须敷设在气体管道和热力管道的下方",{"key":19,"text":20,"correct":21},"C","水平安装时，每节母线槽的支架不应少于1个",true,{"key":23,"text":24,"correct":21},"D","垂直安装时应设置弹簧支承器",{"key":26,"text":27,"correct":21},"E","母线槽安装完毕后，应对穿越防火墙和楼板的孔洞进行防火封堵","CDE","2020版教材P137 本题考查的是供电干线及室内配电线路施工技术要求。母线槽安装前，应测量每节母线槽的绝缘电阻值，且不应小于20MΩ。母线槽应安装在洁净、无渗水的环境，并宜敷设在气体管道和热力管道的下方及液体管道的上方。当不能满足要求时，应采取防水、隔热措施。水平安装时，支架间距不应大于2m，每节母线槽的支架不应少于1个，转弯处应增设支架加强。垂直安装时应设置弹簧支承器。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]