[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113717":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113717,787,2,"多选题","开关柜、配电柜安装施工技术要求包括（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","开关柜、配电柜的基础型钢安装应平直",true,{"key":16,"text":17,"correct":14},"B","配电柜与基础型钢间应用镀锌螺栓连接",{"key":19,"text":20,"correct":21},"C","配电柜安装垂直度允许偏差为1.5%",false,{"key":23,"text":24,"correct":14},"D","成列柜面偏差不应大于5mm",{"key":26,"text":27,"correct":14},"E","高、低压成套配电柜投入运行前必须交接试验合格","ABDE","2020版教材P137 本题考查的是变配电安装施工技术要求。选项C错误，正确描述应为配电柜安装垂直度允许偏差为1.5‰。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]