[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113712":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1113712,787,2,"多选题","室内照明配电箱的安装技术要求不包括（ ）。 A.照明配电箱内应分别设置零线和保护接地汇流排",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","零线和保护线在汇流排上连接",false,{"key":16,"text":17,"correct":14},"B","照明配电箱内每一单相分支回路的电流不宜超过16",{"key":19,"text":20,"correct":21},"C","照明配电箱内每一单相分支回路的灯具数量不宜超过10个",true,{"key":23,"text":24,"correct":21},"D","大型建筑组合灯具每一单相回路光源数量不宜超过50个","CD","2020版教材P140 本题考查的是电气照明施工技术要求。照明配电箱内每一单相分支回路的电流不宜超过16A，灯具数量不宜超过25个。大型建筑组合灯具每一单相回路电流不宜超过25A，光源数量不宜超过60个。插座为单独回路时，数量不宜超过10个。灯具和插座混为一个回路时，其中插座数不宜超过5个。",{"id":6,"name":28,"category":29,"favorite":30},"二建机电工程实务","建筑工程",0]