[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1113687":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1113687,787,2,"多选题","设备保温层施工时，其保温制品的层厚大于100mm时，施工要点有（ ）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","分为两层施工",true,{"key":16,"text":17,"correct":14},"B","分为多层逐层施工",{"key":19,"text":20,"correct":14},"C","各层的厚度宜接近",{"key":22,"text":23,"correct":24},"D","保温层拼缝宽度不应大于50mm",false,{"key":26,"text":27,"correct":24},"E","分为单层施工","ABC","2020版教材P115 1）当采用一种绝热制品，保温层厚度大于或等于100mm，保冷层厚度大于或等于80mm时，应分为两层或多层逐层施工，各层的厚度宜接近。 2）当采用软质或半硬质可压缩性的绝热制品时，安装厚度应符合设计规定。 3）同层应错缝，上下层应压缝，其搭接长度不宜小于100mm。 4）硬质或半硬质材料作保温层，拼缝宽度不应大于5mm 5）用毡席材料时，毡席与设备表面要紧贴，缝隙用相同材料填实。 6）用散装材料时，保温层应包扎镀锌铁丝网，接头用Φ1.4mm镀锌铁丝缝合，每隔捆扎一道镀锌钢丝。 7）施工后的保温层不得覆盖设备铭牌。当保温层厚度高于设铭牌时，可将铭牌周围的保温层切割成喇叭形开口，开口处应规整，并应设置密封的防雨水盖。",{"id":6,"name":31,"category":32,"favorite":33},"二建机电工程实务","建筑工程",0]