[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1112425":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1112425,787,1,"单选题","有关母线的连接固定，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","母线应在找正及固定前，进行导体的焊接",false,{"key":16,"text":17,"correct":14},"B","母线与设备连接完毕后，应进行母线绝缘电阻的测试",{"key":19,"text":20,"correct":21},"C","金属母线与设备连接部位，应设置热胀冷缩或基础沉降的补偿装置",true,{"key":23,"text":24,"correct":14},"D","通过焊接将母线固定在支柱绝缘子上","2020版教材P73 本题考查的是母线和封闭母线安装。母线采用焊接连接时，母线应在找正及固定后，方可进行母线导体的焊接。母线与设备连接前，应进行母线绝缘电阻的测试，并进行耐压试验。母线在支柱绝缘子上的固定方法有：螺栓固定、夹板固定和卡板固定。",{"id":6,"name":27,"category":28,"favorite":29},"二建机电工程实务","建筑工程",0]