[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1112397":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1112397,787,1,"单选题","关于电缆敷设的要求中，正确的有（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","敷设在排管内的电缆，可不采用铠装电缆",false,{"key":16,"text":17,"correct":14},"B","由于电缆防水防潮，电缆排管在敷设电缆前，可不进行疏通，清除杂物及积水",{"key":19,"text":20,"correct":21},"C","排管内穿电缆时，不得损坏电缆护层，可采用无腐蚀性的润滑剂",true,{"key":23,"text":24,"correct":14},"D","穿入管中的电缆数量应符合设计要求，交流单芯电缆可单独穿入钢管内","2020版教材P67 2.电缆敷设要求 （1）敷设在排管内的电缆，应采用铠装电缆。（2）电缆排管在敷设电缆前，应进行疏通，清除杂物及积水。（3）排管内穿电缆时，不得损坏电缆护层，可采用无腐蚀性的润滑剂（粉）。（4）穿入管中的电缆数量应符合设计要求，交流单芯电缆不得单独穿入钢管内。 页，（三〉电缆沟或隧道内电缆敷设的要求：3.高压与低压电力电缆、强电与弱电控制电缆应按顺序分层配置，一般情况宜由上而下配置。",{"id":6,"name":27,"category":28,"favorite":29},"二建机电工程实务","建筑工程",0]