[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1106125":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},1106125,781,2,"多选题","引入火灾报警控制器的电缆或导线，应符合的规定有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","配线应牢固、整齐，避免交叉",true,{"key":16,"text":17,"correct":14},"B","电缆芯线和所配导线应留有不小于200mm的余量",{"key":19,"text":20,"correct":21},"C","端子板的每个接线端，接线不得超过3根",false,{"key":23,"text":24,"correct":14},"D","导线应绑扎成束",{"key":26,"text":27,"correct":14},"E","穿线缆后，进线管孔处应封堵","ABDE","引入火灾报警控制器的电缆或导线，应符合下列规定：①配线应牢固、整齐，避免交叉，端子板不应承受来自线缆的外力；②电缆和导线的端部，均应标明编号，并与图纸一致，字迹清晰不易褪色；③端子板的每个接线端，接线不得超过2根；④电缆芯线和所配导线应留有不小于200mm的余量；⑤导线应绑扎成束；⑥穿线缆后，进线管孔处应封堵。",{"id":6,"name":31,"category":32,"favorite":33},"目标控制（交通工程）","建筑工程",0]