[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1105955":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1105955,781,1,"单选题","开关箱中漏电保护器的额定漏电动作电流不得大于30mA。额定漏电动作时间（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不应大于0.1s",true,{"key":16,"text":17,"correct":18},"B","大于0.1s",false,{"key":20,"text":21,"correct":18},"C","小于0.1s",{"key":23,"text":24,"correct":18},"D","不应小于0.1s","总配电箱中漏电保护器的额定漏电动作电流应大于30mA，额定漏电动作时间应大于0.1s，额定漏电动作电流与额定漏电动作时间的乘积不得大于30mA·s。开关箱中漏电保护器的额定漏电动作电流不得大于30mA。额定漏电动作时间不应大于0.1s。潮湿或有腐蚀介质场所的漏电保护器应采用防潮型产品，额定漏电动作电流不得大于15mA，额定漏电动作时间不得大于0.1s。",{"id":6,"name":27,"category":28,"favorite":29},"目标控制（交通工程）","建筑工程",0]