[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-755-20":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":506},{"id":5,"name":6,"category":7,"favorite":8},755,"电气工程师供配电专业","建筑工程",0,20,50,2321,[13,34,46,54,66,74,82,90,98,110,122,134,142,150,158,166,175,187,199,207,219,227,239,247,255,267,278,286,294,306,314,322,330,338,346,354,362,370,382,390,398,406,418,426,438,450,462,474,484,494],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":24,"analysis":33},1032853,1,"单选题","无彩电转播的体育场馆照明光源的显色指数不应小于（ ）。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","60；",false,{"key":24,"text":25,"correct":26},"B","65；",true,{"key":28,"text":29,"correct":22},"C","70;",{"key":31,"text":32,"correct":22},"D","80.","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":20,"analysis":33},1032855,"某场所照明设计中，按GB 50034—2004《建筑照明设计标准》确定了照度标准值和 允许的LPD限值，同时已选择了某种高效光源和灯具，应（ ）来确定需要的光源数量。",[38,40,42,44],{"key":20,"text":39,"correct":26},"通过照度计算；",{"key":24,"text":41,"correct":22},"按标准规定的LPD限值计算；",{"key":28,"text":43,"correct":22},"桉该场所灯具允许的距离比(L\u002Fh)计算；",{"key":31,"text":45,"correct":22},"该场所布灯相对的对称性。",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":31,"analysis":33},1032857,"某城市交通主干道路为沥青路面，要求路面平均亮度为2.0cd\u002Fm2,设计的路面平均 照度应为（ ）。 A. 15lx； B 201x； C. 25lx; D. 30lx。",[50,51,52,53],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":26},{"id":55,"libraryId":5,"type":15,"typeLabel":16,"stem":56,"options":57,"answer":28,"analysis":33},1032859,"室内灯具按上下空间光通分布可划分为五类，其中直接型灯具的下半球发出的光通 量百分比为（ ）。",[58,60,62,64],{"key":20,"text":59,"correct":22},"90%~60%;",{"key":24,"text":61,"correct":22},"100%~80%;",{"key":28,"text":63,"correct":26},"100%~90%;",{"key":31,"text":65,"correct":22},"100%~60%。",{"id":67,"libraryId":5,"type":15,"typeLabel":16,"stem":68,"options":69,"answer":28,"analysis":33},1032861,"办公室、阅览室等工作房间，顶棚表面反射比宜为（ ）。 A. 0.4~0.5;B 0.5—0.6； C. 0.6~0.9; D. 0.85~0.95。",[70,71,72,73],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":75,"libraryId":5,"type":15,"typeLabel":16,"stem":76,"options":77,"answer":20,"analysis":33},1032863,"光源平均亮度≤20X103cd\u002Fm2,按直接眩光限制要求，开敞式直接型灯具的遮光角 不应小于（ ）。 A. 10°; B 15°; C. 20°; D. 30°。",[78,79,80,81],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":28,"analysis":33},1032865,"办公室、教室等房间一般照明的照度均匀度不应小于（ ）。 A. 0.5; B 0.6; C. 0.7; D. 0.8。",[86,87,88,89],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":91,"libraryId":5,"type":15,"typeLabel":16,"stem":92,"options":93,"answer":20,"analysis":33},1032866,"公共建筑的工作房间及工业厂房内的作业面邻近周围的照度均匀度不应小 于（ ). A. 0.5; B. 0.6; C 0.7; D. 0.8。",[94,95,96,97],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":99,"libraryId":5,"type":15,"typeLabel":16,"stem":100,"options":101,"answer":24,"analysis":33},1032868,"房间或场所内非作业区域的一般照明的照度值不宜低于作业区域一般照明照度值 的（ ）。",[102,104,106,108],{"key":20,"text":103,"correct":22},"1\u002F2;",{"key":24,"text":105,"correct":26},"1\u002F3；",{"key":28,"text":107,"correct":22},"1\u002F4；",{"key":31,"text":109,"correct":22},"1\u002F5。",{"id":111,"libraryId":5,"type":15,"typeLabel":16,"stem":112,"options":113,"answer":24,"analysis":33},1032870,"在有彩电转播要求的体育场馆内的主摄像方向上的场地照明的垂直照度最小值与最 大值之比不宜小于（ ）。",[114,116,118,120],{"key":20,"text":115,"correct":22},"0.3;",{"key":24,"text":117,"correct":26},"0.4；",{"key":28,"text":119,"correct":22},"0.5;",{"key":31,"text":121,"correct":22},"0.7。",{"id":123,"libraryId":5,"type":15,"typeLabel":16,"stem":124,"options":125,"answer":20,"analysis":33},1032872,"光源的相关色温小于3300K时，其色表特征描述为（ ）。",[126,128,130,132],{"key":20,"text":127,"correct":26},"暖；",{"key":24,"text":129,"correct":22},"中间；",{"key":28,"text":131,"correct":22},"冷；",{"key":31,"text":133,"correct":22},"特冷.",{"id":135,"libraryId":5,"type":15,"typeLabel":16,"stem":136,"options":137,"answer":24,"analysis":33},1032874,"办公室、教室、检验室等房间宜选用光源的相关色温为（ ). A. 2700~3000K; B 4000~4500K； C. 5500~6000K; D. 6000~7000K。",[138,139,140,141],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":20,"analysis":33},1032876,"酒吧、咖啡房宜选用相关色温为（ ）的光源。 A. 2700~3300K; B 4000~4500K;C 5500~6000K; D. 6000~7000K。",[146,147,148,149],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":151,"libraryId":5,"type":15,"typeLabel":16,"stem":152,"options":153,"answer":28,"analysis":33},1032878,"长期工作和停留的房间，照明光源的显色指数（R）不宜小于（ ）。 A. 60； B 70; C. 80; D. 90。",[154,155,156,157],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":159,"libraryId":5,"type":15,"typeLabel":16,"stem":160,"options":161,"answer":28,"analysis":33},1032880,"有彩电转播的体育建筑，光源的显色指数（R）不应小于（ ）。 A. 65, B 70; C. 80； D. 90。",[162,163,164,165],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":167,"libraryId":5,"type":15,"typeLabel":16,"stem":168,"options":169,"answer":31,"analysis":33},1032881,"没有精细作业的接待室、休息厅等场所，光源的显色指数（R）不应小于（）。",[170,171,172,173],{"key":20,"text":21,"correct":22},{"key":24,"text":25,"correct":22},{"key":28,"text":29,"correct":22},{"key":31,"text":174,"correct":26},"80。",{"id":176,"libraryId":5,"type":15,"typeLabel":16,"stem":177,"options":178,"answer":24,"analysis":33},1032883,"疏散通道上的疏散照明的照度不宜低于（ ）。",[179,181,183,185],{"key":20,"text":180,"correct":22},"0.2Ix；",{"key":24,"text":182,"correct":26},"0.5lx;",{"key":28,"text":184,"correct":22},"1. Olx;",{"key":31,"text":186,"correct":22},"1.5Ix。",{"id":188,"libraryId":5,"type":15,"typeLabel":16,"stem":189,"options":190,"answer":24,"analysis":33},1032885,"备用照明的照度（除另有规定者外），不宜低于该场所一般照明照度值的（）。",[191,193,195,197],{"key":20,"text":192,"correct":22},"5%;",{"key":24,"text":194,"correct":26},"10%；",{"key":28,"text":196,"correct":22},"25%；",{"key":31,"text":198,"correct":22},"50%。",{"id":200,"libraryId":5,"type":15,"typeLabel":16,"stem":201,"options":202,"answer":28,"analysis":33},1032887,"高度12m的工业厂房，没有选色要求，适宜的光源选择为（ ）。 A.直管荧光灯；B荧光高压汞灯； C.高压钠灯； D.自镇流高压汞灯。",[203,204,205,206],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":208,"libraryId":5,"type":15,"typeLabel":16,"stem":209,"options":210,"answer":20,"analysis":33},1032889,"高度10m的工业厂房，宜选择光通分布类别为（ ）型的灯具。",[211,213,215,217],{"key":20,"text":212,"correct":26},"直接型；",{"key":24,"text":214,"correct":22},"半直接型；",{"key":28,"text":216,"correct":22},"直接间接型；",{"key":31,"text":218,"correct":22},"半间接型。",{"id":220,"libraryId":5,"type":15,"typeLabel":16,"stem":221,"options":222,"answer":20,"analysis":33},1032891,"长60m、宽30m的工业厂房，灯具离作业面高度为8m，宜选用灯具的配光 为（ ）。 A.宽配光； B中配光； C.窄配光； D.特窄配光.",[223,224,225,226],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":228,"libraryId":5,"type":15,"typeLabel":16,"stem":229,"options":230,"answer":28,"analysis":33},1032893,"在满足眩光限制的条件下，开敞式灯具的效率不应小于（ 〉。",[231,233,235,237],{"key":20,"text":232,"correct":22},"65%；",{"key":24,"text":234,"correct":22},"70%；",{"key":28,"text":236,"correct":26},"75%;",{"key":31,"text":238,"correct":22},"80%。",{"id":240,"libraryId":5,"type":15,"typeLabel":16,"stem":241,"options":242,"answer":28,"analysis":33},1032894,"直接安装在可燃材料表面的灯具，应采用有（ ）标志的灯具。",[243,244,245,246],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":248,"libraryId":5,"type":15,"typeLabel":16,"stem":249,"options":250,"answer":31,"analysis":33},1032896,"GB 50034-2004《建筑照明设计标准》规定的照度值系指作业面或参考平面上 的（ ）。 A.初始照度值； B平均照度值； C.最小照度值； D.维持平均照度值。",[251,252,253,254],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":26},{"id":256,"libraryId":5,"type":15,"typeLabel":16,"stem":257,"options":258,"answer":24,"analysis":33},1032898,"道路照明的灯具宜选用防护等级为（）的灯具。",[259,261,263,265],{"key":20,"text":260,"correct":22},"IP44；",{"key":24,"text":262,"correct":26},"IP65；",{"key":28,"text":264,"correct":22},"IP67；",{"key":31,"text":266,"correct":22},"具有双层或加张绝缘的II类。",{"id":268,"libraryId":5,"type":15,"typeLabel":16,"stem":269,"options":270,"answer":28,"analysis":33},1032900,"建筑物外的地埋灯应选用防护等级为（ ）的灯具。",[271,273,275,276],{"key":20,"text":272,"correct":22},"IP56；",{"key":24,"text":274,"correct":22},"IP66;",{"key":28,"text":264,"correct":26},{"key":31,"text":277,"correct":22},"IP68。",{"id":279,"libraryId":5,"type":15,"typeLabel":16,"stem":280,"options":281,"answer":28,"analysis":33},1032902,"实际设计的照度值和规定的照度标准相比，往往有偏差，gb 50034—2004《建筑照 明设计标准》规定一般情况下，允许的偏差是（ ）。 a.不得低于标准值； b.允许+50%~一 10%; c.允许+10%~-10%； d.允许+10%~-5%。",[282,283,284,285],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":287,"libraryId":5,"type":15,"typeLabel":16,"stem":288,"options":289,"answer":31,"analysis":33},1032904,"照明设计中作为照明节能的评价指标是（ ）。 a.选取的照度值； b.选用光源的发光效能； c.选用灯具的效率； d.房间或场所一般照明的照明功率密度",[290,291,292,293],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":26},{"id":295,"libraryId":5,"type":15,"typeLabel":16,"stem":296,"options":297,"answer":24,"analysis":33},1032906,"照明灯具的端电压不宜大于其额定电压的（ ）。",[298,300,302,304],{"key":20,"text":299,"correct":22},"102.5%；",{"key":24,"text":301,"correct":26},"105 °\u002Fo；",{"key":28,"text":303,"correct":22},"107%；",{"key":31,"text":305,"correct":22},"110%。",{"id":307,"libraryId":5,"type":15,"typeLabel":16,"stem":308,"options":309,"answer":28,"analysis":33},1032907,".一般工作场所照明灯具的端电压不宜低于其额定电压的（ ）。 a. 90%； b. 93%; c. 95%； d. 97.5%.",[310,311,312,313],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":315,"libraryId":5,"type":15,"typeLabel":16,"stem":316,"options":317,"answer":24,"analysis":33},1032909,"应急照明、道路照明灯具的端电压不宜低于其额定电压的（ ）。 a. 85%; b. 90%, c. 93%； d. 95%。",[318,319,320,321],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":323,"libraryId":5,"type":15,"typeLabel":16,"stem":324,"options":325,"answer":20,"analysis":33},1032911,"高层建筑内的主通道和楼梯间应设置（ ）。 A.疏散照明； B.安全照明； C.备用照明； D*警卫照明。",[326,327,328,329],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":331,"libraryId":5,"type":15,"typeLabel":16,"stem":332,"options":333,"answer":28,"analysis":33},1032913,"公共建筑内的消防控制中心内应设置（ ）。 a.疏散照明； b.安全照明； c.备用照明； d,警卫照明。",[334,335,336,337],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":339,"libraryId":5,"type":15,"typeLabel":16,"stem":340,"options":341,"answer":24,"analysis":33},1032915,"照明三相配电干线的各相负荷宜分配平衡，最大相负荷不宜超过三相负荷平均值 的（ ）。 a. 110%; b. 115%； c. 120%; d. 125%。",[342,343,344,345],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":347,"libraryId":5,"type":15,"typeLabel":16,"stem":348,"options":349,"answer":24,"analysis":33},1032917,"每一照明单相分支回路的电流不宜大于（ ）。 a. 12a； b. 16a； c. 20a； d. 25a。",[350,351,352,353],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":355,"libraryId":5,"type":15,"typeLabel":16,"stem":356,"options":357,"answer":24,"analysis":33},1032918,"每一照明单相分支回路所接光源数不宜超过（ ）个。 a. 20； b. 25; c. 30; d. 50。",[358,359,360,361],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":363,"libraryId":5,"type":15,"typeLabel":16,"stem":364,"options":365,"answer":31,"analysis":33},1032920,"每一照明单相分支回路连接高强度气体放电灯时，电流不应超过（ ）。 a. 16a； b. 20a; c 25a； d. 30a.",[366,367,368,369],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":26},{"id":371,"libraryId":5,"type":15,"typeLabel":16,"stem":372,"options":373,"answer":28,"analysis":33},1032922,"建筑照明配电干线的功率因数不应低于（ ）。",[374,376,378,380],{"key":20,"text":375,"correct":22},"0.8；",{"key":24,"text":377,"correct":22},"0,85;",{"key":28,"text":379,"correct":26},"0.9;",{"key":31,"text":381,"correct":22},"0.95。",{"id":383,"libraryId":5,"type":15,"typeLabel":16,"stem":384,"options":385,"answer":24,"analysis":33},1032924,"采用（ ）类灯具，其外露可导电部应可靠接地（接pe线)。 a. 0； b.Ⅰ ； c.Ⅱ； d. Ⅲ。",[386,387,388,389],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":391,"libraryId":5,"type":15,"typeLabel":16,"stem":392,"options":393,"answer":20,"analysis":33},1032926,"灯具防触电分类为（ ）类，已被国家标准宣布删除，并将正式实施。 a. 0； b.Ⅰ ； c.Ⅱ； d. Ⅲ。",[394,395,396,397],{"key":20,"text":20,"correct":26},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":399,"libraryId":5,"type":15,"typeLabel":16,"stem":400,"options":401,"answer":28,"analysis":33},1032928,"亮度的代表文字符号是（）。",[402,403,404,405],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":28,"text":28,"correct":26},{"key":31,"text":31,"correct":22},{"id":407,"libraryId":5,"type":15,"typeLabel":16,"stem":408,"options":409,"answer":24,"analysis":33},1032929,"发光强度的单位是（）。",[410,412,414,416],{"key":20,"text":411,"correct":22},"1m;",{"key":24,"text":413,"correct":26},"cd；",{"key":28,"text":415,"correct":22},"cd\u002Fm2 ；",{"key":31,"text":417,"correct":22},"lx。",{"id":419,"libraryId":5,"type":15,"typeLabel":16,"stem":420,"options":421,"answer":24,"analysis":33},1032931,"灯具的光强分布曲线是以光源光通为（）值而编制的. A. lOOOlx； B 10001m, C. lOOOcd; D. 1001m。",[422,423,424,425],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":26},{"key":28,"text":28,"correct":22},{"key":31,"text":31,"correct":22},{"id":427,"libraryId":5,"type":15,"typeLabel":16,"stem":428,"options":429,"answer":28,"analysis":33},1032933,"用利用系数法计算照度，并计 入维护系数，计箅结果是（）值。",[430,432,434,436],{"key":20,"text":431,"correct":22},"平均照度；",{"key":24,"text":433,"correct":22},"最小照度；",{"key":28,"text":435,"correct":26},"维持平均照度；",{"key":31,"text":437,"correct":22},"維持最小照度。",{"id":439,"libraryId":5,"type":15,"typeLabel":16,"stem":440,"options":441,"answer":28,"analysis":33},1032936,"房间的墙面、顶棚面、地面的（ ）对房间的照度有影响。",[442,444,446,448],{"key":20,"text":443,"correct":22},"光亮度；",{"key":24,"text":445,"correct":22},"平整度；",{"key":28,"text":447,"correct":26},"反射比；",{"key":31,"text":449,"correct":22},"折射比。",{"id":451,"libraryId":5,"type":15,"typeLabel":16,"stem":452,"options":453,"answer":31,"analysis":33},1032939,"主要供气体放电灯的三相四线制线路，中性线（N)截面选择是（ ）。",[454,456,458,460],{"key":20,"text":455,"correct":22},"不小于相线截面；",{"key":24,"text":457,"correct":22},"为相线截面的2倍；",{"key":28,"text":459,"correct":22},"满足不平衡电流要求；",{"key":31,"text":461,"correct":26},"满足不平衡电流及谐波电流的要求，且不应小于相线截面。",{"id":463,"libraryId":5,"type":15,"typeLabel":16,"stem":464,"options":465,"answer":24,"analysis":33},1032942,"髙层建筑应根据其使用性质、火灾危险性、疏散和扑救难度等分为（）。",[466,468,470,472],{"key":20,"text":467,"correct":22},"一级和二级；",{"key":24,"text":469,"correct":26},"—类和二类；",{"key":28,"text":471,"correct":22},"特级、一级和二级；",{"key":31,"text":473,"correct":22},"—类、二类和三类。",{"id":475,"libraryId":5,"type":15,"typeLabel":16,"stem":476,"options":477,"answer":28,"analysis":33},1032945,"火灾自动报警系统的保护对象应根据其使用性质、火灾危险性、疏散和扑救难度等分为（）。",[478,479,481,482],{"key":20,"text":467,"correct":22},{"key":24,"text":480,"correct":22},"一级、二级和三级；",{"key":28,"text":471,"correct":26},{"key":31,"text":483,"correct":22},"特级、一级、二级和三级。",{"id":485,"libraryId":5,"type":15,"typeLabel":16,"stem":486,"options":487,"answer":28,"analysis":33},1032947,"控制中心报警系统宜用于（ ）保护对象。",[488,489,490,492],{"key":20,"text":467,"correct":22},{"key":24,"text":480,"correct":22},{"key":28,"text":491,"correct":26},"特级、一级；",{"key":31,"text":493,"correct":22},"特级。",{"id":495,"libraryId":5,"type":15,"typeLabel":16,"stem":496,"options":497,"answer":24,"analysis":33},1032949,"建筑高度超过1OOm的高层建筑，除（）外，均应设火灾自动报警系统。",[498,500,502,504],{"key":20,"text":499,"correct":22},"厕所和储藏间；",{"key":24,"text":501,"correct":26},"游泳池、卫生间、溜冰场；",{"key":28,"text":503,"correct":22},"卫生间、开水间；",{"key":31,"text":505,"correct":22},"卫生间、管道井。",[507,510,513,516,519,522],{"id":15,"name":508,"category":7,"favorite":509},"领导干部任职前廉政法规知识测试题",92,{"id":511,"name":512,"category":7,"favorite":15},595,"建筑结构与设备",{"id":514,"name":515,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":517,"name":518,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":520,"name":521,"category":7,"favorite":8},534,"BIM工程师",{"id":523,"name":521,"category":7,"favorite":8},535]