[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1036673":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1036673,755,2,"多选题","—台风机配用额定功率为55kW的交流电动机，三角形接线，额定电压380V，额 定电流为102A。该电动机采用热继电器作过载和断相保护器件。为提高运行功率因数及减少启动时对电网的冲击，设计方案中考虑星-三角启动方式和电动机单独补偿电容器。请回 答以下热继电器设置及参数计算的有关问题。 为提高系统运行功率因数，对风机的电动机单独设置补偿电容器。设置补偿电容器 后，以下热继电器的设置方案的调整，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","如电容器接入位置在热继电器之前，整定电流值与原整定电流相同；",true,{"key":16,"text":17,"correct":18},"B","如电容器接入位置在热继电器之前，整定电流值为原整定电流1.5倍；",false,{"key":20,"text":21,"correct":14},"C","如电容器接入位置在热继电器之后，整定电流值为原整定电流0.92~0.95倍；",{"key":23,"text":24,"correct":18},"D","如电容器接入位置在热继电器之后，整定电流值与原整定电流相同；","AC","A、C 《工业与民用配电设计手册》（第三版）P670。",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]