[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1036669":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1036669,755,2,"多选题","—台风机配用额定功率为55kW的交流电动机，三角形接线，额定电压380V，额 定电流为102A。该电动机采用热继电器作过载和断相保护器件。为提高运行功率因数及减少启动时对电网的冲击，设计方案中考虑星-三角启动方式和电动机单独补偿电容器。请回 答以下热继电器设置及参数计算的有关问题。 为避免电动机启动时间太长而导致热继电器误动作，下列措施正确有效的是( )o",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","提高热继电器的整定电流；",false,{"key":16,"text":17,"correct":18},"B","将热继电器经速饱和电流互感器接入主回路；",true,{"key":20,"text":21,"correct":14},"C","减小热继电器的整定电流；",{"key":23,"text":24,"correct":18},"D","在启动过程中短接热继电器过载保护器件。","BD","B、D《通用用电设备配电设计规范》0650055-1993第2.4.8条，《工业与民用配电设计手 册》（第三版）P67O。",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]