[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1036665":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1036665,755,2,"多选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW,额定电压交流三相 6kV,额定电流0.144kA,额定启动电流倍数6倍，电动机启动转矩与额定转矩之比为 1.1, 6kV母线短路容量为40MVA,母线上预接负荷的无功功率为1Mvar,要求启动时母 线电压不低于额定电压的85%。选择启动方式和计算启动的有关参数。 下列（ ）启动方式可能作为本台电动机的启动方式。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","Y—△降压启动；",false,{"key":16,"text":17,"correct":18},"B","自耦变压器降压启动；",true,{"key":20,"text":21,"correct":18},"C","电抗器降压启动；",{"key":23,"text":24,"correct":18},"D","全压启动。","BCD","B、C、D《工业与民用配电设计手册K第三版）P267，《钢铁企业电力设计手册》(下）P90，《电 气传动自动化技术手册》(第2版）P317。",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]