[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1036585":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1036585,755,2,"多选题","以下原则（ ）符合低压电动机的启动器（包括启动控制电器及过载保护电器） 与短路保护器的协调配合要点。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","在过栽保护器与短路保护器两条时间一电流特性曲线交点所对应的电流（大致相当 于电动机堵转电流）以下，短路保护器不应动作；",true,{"key":16,"text":17,"correct":14},"B","电动机回路上的电流大于电动机堵转电流时，短路保护电器应在过载保护电器动作 之前动作；",{"key":19,"text":20,"correct":21},"C","电动机回路上的电流大于电动机堵转电流时，过载保护电器应在短路保护电器动作 之前动作；",false,{"key":23,"text":24,"correct":21},"D","1类配合为启动器短路情况下不应对设备和人身造成危害，且应能继续使用。","AB","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]