[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1035776":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1035776,755,2,"多选题","发电厂、变电所电气设备接地线的截面应进行热稳定校验，接地线的温度应符合 的要求是（ ）。 A.在有效接地系统和低电阻接地系统中，接地线的短时温度：钢线不超过500℃、铜 线不超过400℃、铝线不超过300℃;",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","在有效接地系统和低电阻接地系统中，接地线的短时温度：钢线不超过400℃、铜 线不超过450℃、铝线不超过300℃;",false,{"key":16,"text":17,"correct":18},"B","在不接地、经消弧线围和髙电阻接地系统中，接地线的长时间温度：地上敷设者不 大于150℃、地下敷设者不大于100℃;",true,{"key":20,"text":21,"correct":18},"C","与架空送配电线路相连的6~66 kV电气设备接地线，应按两相异地短路校验热稳",{"key":23,"text":24,"correct":18},"D","定，接地线的短时温度：钢线不超过400℃、铜线不超过450℃、铝线不超过300℃。","BCD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]